APC MGE Galaxy 5500 Double-conversion (Online) 120 kVA 108000 W
120kVA, 108 kW, 400V, 3-Phase, Hard Wire In, Hard Wire Out, LCD
APC MGE Galaxy 5500
Out of stock
Custom Spanstor Build & Test
As part of our Spanstor Build & Test services, any enclosure bought with drives, we will include all firmware installations, physical drive installations, RAID/cache configurations and drive bad-sector checks, all at no additional cost. If you have any questions, please contact our friendly sales team by chat, phone or email.
EU CoC for UPS
Ensures that UPSs sold in the EU are highly efficient
Multiple levels of service
With the option of packages or individual service components, our services are structured to allow you to pick and choose what you would like APC to do for you.
Technical support
Our experienced technical support engineers are available to answer your questions, giving you peace of mind knowing the help you need is there when you need it.
Front-access servicing
Simplifies installation and UPS maintenance while minimizing space requirements.
Wide input voltage range
Designed for harsh electrical environments to save battery life.
ECO Mode
Operating mode that by-passes unused electrical components in good power conditions to achieve high operating efficiency without sacrificing protection
Input power factor correction
Minimizes installation costs by enabling the use of smaller generators and cabling.
Predicitive failure notification
Provides early-warning fault analysis ensuring proactive component replacement.
Integrates with StruxureWare Central
An IT-ready, scalable access monitoring system that collects, organizes, and distributes critical alerts, surveillance video and key information, providing a unified view of complex physical infrastructure environments from anywhere on the network
Network management capability
Full-featured network management interfaces that provide standards-based management via Web, SNMP, and Telnet.
LED Indicators
Provide easy-to-read status of the unit and utility power conditions.
LCD graphics display
Text and mimic diagrams that display modes of operation, system parameters and alarms.
Flexible Design
Available in a wide range of configurations to suit any operating environment.
Generator compatible
Ensures clean, uninterrupted power to protected equipment when generator power is used.
Parallel-capacity capable
Increases total power capacity by using multiple uninterruptible power supplies simultaneously.
Advanced electrical features
Excellent power conditioning, very low harmonic distortion through IGBT rectifier, input power factor correction, and high power efficiency
Parallel-redundant capable
Power the connected equipment with multiple uninterruptible power supplies to increase system redundancy
Dual mains input
Increases availability by allowing the UPS to be connected to two separate power sources.
Frequency and voltage regulation
Gives higher application availability by correcting poor frequency and voltage conditions without using the battery.
Power | |
---|---|
Output power | 108000 W |
Input operation voltage (min) | 250 V |
Input operation voltage (max) | 470 V |
Output operation voltage (min) | 380 V |
Output operation voltage (max) | 415 V |
Maximum current | 173 A |
Efficiency | 93.4% |
Output voltage Total Harmonic Distortion (THD) | 1% |
Input current Total Harmonic Distortion (THD) | 3% |
Crest factor | 3:1 |
Output power capacity | 120 kVA |
Performance | |
UPS topology | Double-conversion (Online) |
Waveform | Sine |
Number of output phases | 3 |
Number of input phases | 3 |
LED indicators | USB |
Power protection features | Overload |
Noise level | 65 dB |
Features | |
UPS topology | Double-conversion (Online) |
Waveform | Sine |
Number of output phases | 3 |
Number of input phases | 3 |
Output power | 108000 W |
Input operation voltage (min) | 250 V |
Input operation voltage (max) | 470 V |
Output operation voltage (min) | 380 V |
Output operation voltage (max) | 415 V |
Maximum current | 173 A |
Efficiency | 93.4% |
Power protection features | Overload |
Output voltage Total Harmonic Distortion (THD) | 1% |
Noise level | 65 dB |
Input current Total Harmonic Distortion (THD) | 3% |
Crest factor | 3:1 |
Output power capacity | 120 kVA |
Input frequency | 45/65 Hz |
Ports & interfaces | |
AC outlet types | Terminal |
Power plug | Terminal |
Battery | |
Battery voltage | 432 V |
Battery recharge time | 10 h |
Design | |
International Protection (IP) code | IP20 |
Form factor | Tower |
LED indicators | USB |
Product colour | Black, Grey |
Display | LCD |
Certification | CE, EN/IEC 62040-3, IEC 62040-1-2, IEC 62040-2, ISO 9001, TUV, VDE |
Operational conditions | |
Operating temperature (T-T) | 0 – 40 °C |
Storage temperature (T-T) | -20 – 45 °C |
Operating relative humidity (H-H) | 0 – 95% |
Storage relative humidity (H-H) | 0 – 95% |
Operating altitude | 0 – 999 m |
Non-operating altitude | 0 – 120000 m |
Weight & dimensions | |
Weight | 520 kg |
Width | 712 mm |
Height | 1900 mm |
Depth | 850 mm |
Package width | 980 mm |
Package depth | 960 mm |
Package height | 2030 mm |
Package weight | 540 kg |
Packaging data | |
Package width | 980 mm |
Package depth | 960 mm |
Package height | 2030 mm |
Package weight | 540 kg |
Certificates | |
Certification | CE, EN/IEC 62040-3, IEC 62040-1-2, IEC 62040-2, ISO 9001, TUV, VDE |
Other features | |
Output connections | HardWire 4-wire (3PH + G) |
Input connection type | HardWire 4-wire (3PH + G), HardWire 4-wire (3PH + N) |
Nominal output voltage | 400 V |
Nominal input voltage | 400 V |
Communication options, cards | SmartSlot |